1.maje 1220
756 61  Roznov pod Radhostem
Tel.: +420 571 653 990



Multiloggers Transmitters
And Regulators
Recorder with Printer

T5140 CO2 concentration transmitter with 4-20mA output, built-in carbon dioxide sensor

code: T5140
CO2 - carbon dioxide level sensor.

carbon dioxideCO2 concentration transmitter with 4-20mA output is built in a durable case. Output range is user adjustable. Large dual line LCD is an advantage. Display is possible to switch off.

Included in delivery:

  • T5140 sensor
  • Traceable calibration certificate
  • Quick start manual
  • Free program TSensor for configuring of the transmitter is ready to Download

Send request


The CO2 - carbon dioxide level is recently regarded as an important parameter that substantially determines the quality of the interior climate. Especially in buildings where many people gather, such meeting rooms, hospitals, schools, cinemas, theatres and care centres. With the help of CO2 sensor engineers, technical advisors, environmental experts and health specialists can optimize the ventilation for creation of a healthy interior climate.

Method of CO2 sensor multipoint calibration leads to an excellent accuracy measurements of CO2 in the entire of operating temperature range. With this sensor is the device able to meet the demanding requirements for outdoor use. The measurement principle is based on the NDIR principle  with dual wavelength, which automatically compensates for aging of the sensor. The sensor is resistant against the pollution and provides maintenance-free operation and excellent long-term stability.


APPLICATIONS - measuring of CO2 level at:

  • building HVAC management
  • climate technology
  • schools, universities
  • meeting rooms, hospitals, cinemas, theatres
  • weather stations

Transmitter contains a microprocessor based control circuitry in a durable plastic case with connection terminals.

The CO2 concentration sensor is built inside the case.

Large dual line LCD is an advantage. Display is possible to switch off. Computerized design ensures maximum long term stability and failure indication.

Measured CO2 concentration values are converted to 4-20mA current output.

Output is adjusted to maximum range from the manufacturer.
To adjust other range by the user buying of SP003 cable is necessary - see Optional accessory.
Free configuration program TSensor for transmitter adjustment is ready to download anytime.

If different adjustment of output range is required, please specify required range in the order. Adjustment is free of charge.

Ordering example: Transmitter T5140, output 0 to 2000ppm


Typical application wiring

Technical Data

Technical parameters Value
Output 4-20mA
Measured Value CO2
Construction Type Ambient Air
Design Industrial
Temperature Measuring Range to °C
Relay Output No
Two-State Input No
Lcd Display Yes
PoE No
Range of CO2 concentration measurement 0 to 2000 ppm
Accuracy of CO2 concentration measurement ±(50ppm +2% from reading) at 25°C and 1013hPa
Temperature operating range -30 to +60°C
IP protection IP30
Power 9-30Vdc
Dimensions 88.5 x 94 x 39.5 mm (W x H x D)
Weight approximately 145g