IoT Wireless Temperature Datalogger for 2 external probes, with two two-state inputs, built-in 2G modem and Flat Rate SIM Card
IoT Wireless Datalogger kit with built-in GSM modem and Flat Rate SIM Card allows the instant connection to the COMET Cloud.
GSM Datalogger is designed to record from two external temperature probes and two two-state inputs. In case of exceeded set limits e-mail is sent from the COMET Cloud.
Alarms are also indicated locally by LED, LCD and acoustically by built-in beeper.
The recording is performed in a non-volatile electronic memory. The data can be transferred to a PC via included USB-C cable.
GSM recorder includes Traceable calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
-
codeU0843Msim
-
Warranty3 years
Product variants
Technical data
Measured value
Temperature
Two-state signal
TEMPERATURE SENSOR - external probe Pt1000
Measuring range
-200 to +260 °C
Accuracy
±0.2°C; ±0,2 % of the measurement value in a range of +100 to +260 °C
Resolution
0.1 °C
Response time t90 of temperature measurement (temperature step 20°C, air flow approximately 1m/s)
according to the connected probe
BINARY INPUT
Parameters of the voltage contact
„L“ level input voltage:< 0,4 V(*);
„H“ level input voltage:> 2 V;
Minimum voltage applicable:0 V;
Maximum voltage applicable:+30 V DC
„H“ level input voltage:> 2 V;
Minimum voltage applicable:0 V;
Maximum voltage applicable:+30 V DC
Parameters of the voltage-free contact
Contact resistance in „switched-on“ state:< 10 kOhm;
Contact resistance in the „switched-off“ state:> 300 kOhm;
Contact voltage in the „switched-off“ state:ca 3 V;
Minimum state duration necessary for latching the state:1s
Contact resistance in the „switched-off“ state:> 300 kOhm;
Contact voltage in the „switched-off“ state:ca 3 V;
Minimum state duration necessary for latching the state:1s
GSM MODEM PARAMETERS
Quad-band
850/900/1800/1900MHz
Compliant to GSM
Phase2/2+
GPRS
GPRS mobile station class B
Class 4
2W @ 850/900MHz
Class 1
1W @ 1800/1900MHz
GENERAL TECHNICAL DATA
Operating temperature
-20 to +60 °C
Channels
2x external temperature probe, 2x binary input
Memory
500,000 values in noncyclic logging mode; 350,000 values in cyclic record mode
Recording interval to the internal memory
adjustable from 1 second to 24 hours
Recording interval to the COMET Cloud
from 5 minutes
Interval for measuring and evaluating alarms
adjustable 1 s, 10 s, 1 min
Recording mode
noncyclic - data logging stops after filling the memory
cyclic - after filling memory oldest data is overwritten by new
cyclic - after filling memory oldest data is overwritten by new
Real time clock
year, leap year, month, day, hour, minute, second
Power
rechargeable Li-Ion battery A8200, 3.6V/5200mAh
Protection class
IP20
Dimensions
61 x 93 x 53 mm, with antenna 120 x 93 x 53 mm
Weight (including batteries)
approx. 270 g
Warranty
3 years